Internally reviewed against the linked official sources on 26 November 2026. General information and suggested recordkeeping practices only; not independent technical certification or a determination of compliance for a particular building. Confirm requirements, applicable editions and local authority directions for your premises.
What to record
Regulation 10 of the Fire Safety (England) Regulations 2022 applies in England. For buildings with two or more domestic premises whose top storey exceeds 11 metres (measure under regulation 3), the Responsible Person must check communal fire doors at least quarterly and make best endeavours to check doors at flat entrances every year. Both checks include self-closing function. Keep records of steps taken for flat entrance checks, including attempts to secure access. Requirements to give residents fire-door information apply more broadly to covered buildings with communal escape areas. These checks do not replace the wider fire risk assessment.
Worked example (fictional)
C-014 fails to self-close; log, arrange repair and attach a dated follow-up. F-031 inaccessible: record attempts and plan further access; do not mark as inspected.